| 1. Status. |
3m |
Check operating status. |
Note: With computer room chilling units always check with computer staff before service or maintenance. Do not only rely on the microprocessor readouts, always check against calibrated equipment if in any doubt. |
| 2. Refrigeration circuits |
3m |
Check circuit pressures and superheat temperatures. Check alarm and run lights and remote alarm lights associated with packs. |
Refrigeration circuits should be alternated at least every three months by means of the 'lead/leg' selector switch. Where operating information is displayed on central console, check that no discrepancies exist between display and master gauges, if these do occur report and change transducer(s). For non electronic systems check installed gauges against master gauges. |
| 3. Refrigerant |
3m |
Check for refrigerant and all leaks. |
Refrigeration circuits should be alternated at least every three months by means of the 'lead/leg' selector switch. Where operating information is displayed on central console, check that no discrepancies exist between display and master gauges, if these do occur report and change transducer(s). For non electronic systems check installed gauges against master gauges. |
| 4. Expansion valves |
3m |
Adjust if necessary. |
Only by a competent technician. |
| 5. Chilled water supply |
3m |
Check supply and return water temperatures. |
If closed system check for presence of water. |
| 6. Glycol |
3m |
Check glycol concentration in chilled water. |
If concentration has fallen check pipework for leaks as per item 8. |
| 7. Chiller water flow rate. |
3m |
Check that this is in accordance with the manufacturer s recommended figure. |
|